| Sign In | Join Free | My chinaqualitylighting.com |
|
Brand Name : PR
Model Number : PR 6437D
Certification : CO
Place of Origin : Denmark
MOQ : 1
Price : 200-400usd
Payment Terms : T/T
Supply Ability : 99pcs 4-6 weeks
Delivery Time : 5-7 work days
Displaytype : LCD, Analog Dial
Pressurerange : 0 to 10,000 psi
Accuracy : ±0.1% FS
Calibration : Factory Calibrated, Field Calibratable
Application : Industrial, HVAC, Automotive, Aerospace
Operatingtemperature : -40°C to 85°C
Mountingoptions : Panel, Wall, Pipe
Productname : Pressure Measurement Instruments
Responsetime : ≤ 1 ms
Material : Stainless Steel, Brass
Protectionrating : IP65, IP67
Outputsignal : 4-20 mA, 0-10 V, Digital
Measurementtype : Gauge, Absolute, Differential
Connectiontype : Threaded, Flanged
Powersupply : 24 V DC
| Operating temperature | -50°C to +85°C (standard) -40°C to +80°C (SIL) |
| Storage temperature | -50°C to +85°C |
| Calibration temperature | 23...25°C |
| Relative humidity | < 99% RH (non-cond.) |
| Protection degree | IP20 |
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Weight (single input / dual input) | 150 g / 160 g |
| Wire size | 0.13...2.08 mm² AWG 26...14 stranded wire |
| DIN rail type | DIN EN 60715/35 mm |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 2...25 Hz: ±1.6 mm 25...100 Hz: ±4 g |
| Supply voltage | 7.5*...30** VDC |
| Power dissipation, per channel | ≤ 850 mW |
| Additional min. supply voltage when using test terminals | 0.8 V |
| Min. load resistance at >37 V supply | (Vsupply - 37) / 23 mA |
| Isolation voltage, test / working | 2.5 kVAC / 42 VAC |
| Response time | 75 ms |
| Programmable damping | 0...60 s |
| Warm-up time | < 5 min. |
| Start-up time | < 2.75 s |
| Long-term stability | ±0.05% of span / year (±0.18% of span / 5 years) |
| Signal dynamics, input / output | 24 bit / 18 bit |
| RTD type | Pt10...10000, Ni10...10000, Cu5...1000 |
| Basic accuracy, e.g. Pt100 | ≤ ±0.04°C |
| Cable resistance per wire | 50 Ω (max.) |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Basic accuracy, e.g. TC K | ≤ ±0.25°C |
| Normal range, programmable | 3.8...20.5 / 20.5...3.8 mA |
| Extended range (output limits), programmable | 3.5...23 / 23...3.5 mA |
| Basic accuracy | ≤ ±1.6 μA (0.01% of full output span) |
| HART protocol revisions | HART 7 and HART 5 |
| ATEX | DEKRA 16ATEX0047X |
| IECEx | IECEx DEK. 16.0029X |
| CSA | CSA 16.70066266 |
| SIL | SIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508 |
|
|
2 Wire HART 7 Temperature Transmitters PR 6437D Single Or True Dual Inputs Images |